Noise Barrier Acoustic Ratings: DLR, DL-alpha and Insertion Loss

In short: DLR is the laboratory rating of airborne sound insulation to EN 1793-2. DL-alpha is the laboratory rating of absorption to EN 1793-1. Insertion loss is the reduction measured in the field to ISO 10847, and it includes the geometry, the seals and every gap. A specification that names only DLR has specified a panel, not a barrier.

The confusion is understandable, because all three appear as single numbers in decibels and all three are described as performance. They answer different questions, and the one that predicts what a resident hears is the third.

What is DLR?

DLR is the single number rating of airborne sound insulation for a noise reducing device, defined in EN 1793-2. It is derived from the third octave insulation measured in a laboratory, weighted against a standardized traffic noise spectrum.

  • It describes how much sound the panel stops from passing through it.

  • It is measured on a specimen with sealed edges, so it does not include site gaps.

  • It is the number used to compare products on equal terms.

  • It says nothing about reflections, which is the other half of barrier behaviour.

What is DL-alpha?

DL-alpha is the single number rating of sound absorption, defined in EN 1793-1. It describes how much of the sound arriving at the barrier face is absorbed rather than reflected.

Absorption matters in two situations. On the barrier face towards the receiver, it reduces the sound that would otherwise reflect back from a parallel wall on the opposite side of the road. On the underside of a canopy or a tunnel soffit, it reduces the build-up of reflected energy in the enclosed space.

Why is DLR not the same as Rw?

Rw is the weighted sound reduction index of a building element, defined in ISO 717-1, and it is weighted against a different reference spectrum. A panel can have a high Rw and a lower DLR, or the reverse, because the weighting curves and the frequency range of interest are not the same.

In practice, quoting Rw for a roadside barrier is a category error: it may be a legitimate laboratory number, but it is not the rating that EN 14388 asks for and it cannot be compared with a competitor's DLR.

What is insertion loss, and why does it differ from DLR?

Insertion loss is the difference in sound level at a receiver with and without the barrier, measured in place. It is a property of the whole installation, not of the panel.

  • Geometry: a barrier that is too short in relation to the source and receiver heights produces little insertion loss regardless of DLR.

  • Leaks: gaps at the base, at penetrations and at panel joints short-circuit the panel.

  • Reflections: a reflective barrier between two parallel walls can reduce its own benefit.

  • Ground and terrain: the same barrier over soft ground and over hard ground gives different results.

What are typical values?

RatingTypical rangeWhat it tells you
DLR (EN 1793-2)About 20 dB to 30 dB for solid metal or concrete panelsPanel insulation quality
DL-alpha (EN 1793-1)About 0.6 to 0.9 for absorptive panels; low for reflectiveHow much is absorbed rather than reflected
Insertion loss in situ (ISO 10847)Commonly single figures to low teens at a receiverWhat the installation actually achieves

The gap between the DLR and the measured insertion loss is not a defect; it is the difference between a material property and a system result. It is, however, the reason a design prediction should never be built by taking DLR directly.

How do you read a test report?

  • Check the standard, and that the laboratory is accredited for it.

  • Check what was tested: the complete panel assembly, or only a flat specimen of the core.

  • Check the mounting and the specimen size, because edge sealing and frame effects change the result.

  • Check the frequency range and whether the third octave data is included, not only the single number.

  • Check that the product tested is the product specified, including core density and facing.

Why can two barriers with the same DLR perform differently?

Because on site the differences are in the details. Two panels rated at the same DLR will diverge once one is installed with a sealed base and tight joints and the other with a 20 mm gap along the bottom and unsealed penetrations for lighting columns.

Height and position relative to the source and receiver then dominate: a taller barrier of lower DLR usually outperforms a shorter one of higher DLR, because diffraction over the top is the controlling path.

What should a specification ask for?

  • DLR to EN 1793-2, quoted for the complete panel.

  • DL-alpha to EN 1793-1 where absorption is required, with the intended face identified.

  • An in-situ verification by ISO 10847 after installation, with the number of positions stated.

  • Sealing and penetration details on the drawings, since they decide whether the ratings survive.

  • Test reports, not manufacturer statements, for both ratings.

Standards and references

  • EN 1793-1 — sound absorption, DL-alpha.

  • EN 1793-2 — airborne sound insulation, DLR.

  • EN 1793-3 — normalized traffic noise spectrum used for the ratings.

  • EN 14388 — product specification for road traffic noise reducing devices.

  • ISO 10847 — in-situ determination of insertion loss.

  • ISO 717-1 — weighted sound reduction index Rw, a different rating.

Related reading: structure and panel selection, panel specifications, and installation tolerances.

Noise Barrier Acoustic Ratings: DLR, DL-alpha and Insertion Loss

Frequently asked questions

What does DLR mean on a noise barrier?

DLR is the single number airborne sound insulation rating defined in EN 1793-2. It is measured in a laboratory on a sealed specimen and weighted against a standardized traffic noise spectrum.

Is DLR the same as Rw?

No. Rw is a building acoustics rating to ISO 717-1, weighted against a different spectrum. A panel can have a high Rw and a lower DLR, so the two cannot be compared or substituted in a specification.

Why is measured insertion loss lower than DLR?

Because insertion loss includes geometry, diffraction over the top, leaks at the base and penetrations, and reflections. DLR describes only how much sound passes through the panel itself.

What DLR should a road noise barrier have?

Solid metal or concrete panels typically achieve around 20 dB to 30 dB. Above that, the limiting path is usually diffraction over the top rather than transmission through the panel.

Should insertion loss be measured after installation?

Yes, to ISO 10847, at several positions on both sides. It is the only measurement that captures whether the seals, joints and penetrations allow the rated performance to be delivered.

Contact Us

Imfornation

Railway Station Noise: Platforms, Plant and ApproachesSign Gantries and Noise Barriers: Passing Structures Through a Barrier LineHospital Noise Barrier: Ward Targets, Height and CleanabilityTemporary Noise Barrier: Rent or Buy, and What Drives CostNoise Barrier Fire Performance: Reaction to Fire and Escape RoutesWarehouse Noise Barrier: Docks, Plant and YardsAirport Noise Barrier: Ground Noise, Run-Up and Plant3D-Welded Mesh fencing systemAnti-Climb Fence Specification: 358 Mesh, Paladin Pales and 3D PanelsConstruction Site Noise Barriers: Temporary Screens That Move With the Works5m High Noise BarrierHighway Noise Barrier Foundation: Piles, Footings and Soft Ground1Data Centre Cooling Noise: Louvre Screens and AirflowIndustrial Noise Barrier SystemRail and Transit Noise Barrier: Lines, Stations, Depots358 Security Fence: Mesh, Wire and Anti-Climb SpecificationLaboratory Noise: Fume Hoods, Compressors and VibrationTunnel Portal Noise: Hoods, Barriers and AbsorptionQuarry Noise Control: Crushers, Screens and BlastingAt-Grade Railway Noise Barrier: Level Crossings and Track AccessDouble Wire Fence: 868 and 656 Panels, Posts and Fixings3m High Noise BarrierRoad Viaduct Noise Barrier: Deck Edge, Parapet and Load Limits6m High Noise BarrierMetro Depot Noise Barrier: Enclosure for Depots and Over-Track DevelopmentStadium Noise Barrier: Crowd, PA and Plant CompoundsToll Plaza Noise: Canopy Reflection and AccelerationSolar Noise Barrier Cost: What Drives the Price and the PaybackNoise Barrier Acoustic Ratings: DLR, DL-alpha and Insertion LossNoise Barrier Height: How the Height Is Actually SetPerforated Metal Noise Barrier: Open Area and AbsorptionResidential Noise Barrier: Height, Planning and AppearanceSchool Noise Barrier: Cutting Traffic Noise at the Classroom0.85 NRC Noise Barrier WholesalePlace of Worship Noise Barrier: Chimes, PA and PlantNoise Barrier Maintenance: Inspection and RepairTunnel Approach Noise Barrier: Open Cut, Portal and Cut-and-CoverCutting and Embankment Noise Barrier: Section GeometryConstruction Site Fencing: Temporary Panels, Welded Mesh or HoardingSubstation and Transformer Noise Barriers: Controlling Low-Frequency HumHighway Service Area Noise Barrier: HGV Parking, Plant and NeighboursTemporary Fence: Panels, Ballast and Wind Load on SiteRailway and HSR Noise Barriers: Design for Speed and ClearanceRetrofitting Noise Barriers to an Existing Highway: Constraints and Sequence