Thermal Movement in Noise Barriers: Joints, Slots and Restraint

In short: a steel barrier moves because steel expands with temperature, and a run of panels restrained at both ends will either buckle or tear its fixings. Movement is normal, predictable and small per metre, but it accumulates over a long run and it has to be given somewhere to go.

  • Allow roughly a millimetre of movement per metre of steel for a typical seasonal temperature range, and check the figure against the actual range.

  • Movement is absorbed at joints, at slip connections and at the ends of a run. Never at the fixings.

  • Transparent panels move more than metal panels and behave differently under restraint.

  • The acoustically invisible consequence is a joint that opens and starts to leak air, and therefore sound.

Why does a steel barrier move?

Because the coefficient of thermal expansion for steel is roughly twelve parts per million per degree, which over a twenty metre run and a fifty degree seasonal swing produces a movement of about twelve millimetres. That is small in absolute terms and entirely predictable, but it is large compared with the tolerances in a bolted connection.

Aluminium moves about twice as much as steel. Polymeric panels move several times more again. A mixed-material barrier therefore has differential movement between its components, not just overall movement of the run.

How much movement is normal?

For steel, of the order of a millimetre per metre over a typical seasonal range, so a fifty metre run moves about fifty millimetres in total if it is free at one end. The number that matters for the design is not the total but the movement between two adjacent fixed points, because that is what a joint or a fixing has to absorb.

State the design temperature range explicitly. A barrier designed for a European temperate range and installed in a continental or desert climate will see a much larger swing than the detail assumed.

Where should movement be absorbed?

At three locations. At panel-to-panel joints, where a sliding or overlapping detail lets one panel move relative to the next. At post-to-foundation connections, where a slotted base plate allows the post to move without loading the anchor. And at the ends of a long run, where an expansion joint or a free end allows the whole run to grow and shrink.

What must not absorb movement is the panel-to-post fixing. A fixing that is required to slide will eventually work loose, and a fixing that is rigid will transfer the movement into the panel and crack it at the hole.

What happens if a run is fully restrained?

The movement goes into stress instead of displacement, and that stress adds to the wind load case the run was already designed for. The run will either buckle out of plane at its weakest point, which is usually a joint with the least rotational stiffness, or it will tear at the fixings. Buckling is visible and alarming; tearing at the fixings is invisible until the panel comes loose.

In acoustic terms both are bad, because a buckled panel opens its joints and a torn fixing creates a gap. A restrained run also transmits structure-borne vibration into the foundation, which can be a path for low frequency sound into a structure that the barrier was meant to protect.

How do panel joints accommodate movement?

With a lap, a tongue and a gap, or a cover strip. The lap allows movement in the plane of the panel while keeping the acoustic path tortuous. The tongue and gap works the same way with a defined clearance. A cover strip hides the joint and provides a second line of defence, but it must be fixed to one side only so that it can slide over the other.

The joint detail that fails is the one where both sides are bolted through the same cover. It looks rigid and weatherproof, and it transfers the whole movement into the bolts.

Why do transparent panels behave differently?

Because they have a much higher coefficient of expansion and a much lower tolerance for point load. An acrylic panel moves several times as much as a steel panel of the same length, and it will crack rather than yield if the movement is restrained at a fixing. Polycarbonate is tougher but still moves more than metal.

The practical rule is that transparent panels need oversized holes, compliant washers and a joint that is generous relative to the metal joint next to it. A transparent panel detailed like a metal panel will fail in its first hot season. Fixing and joint tolerances for specific panel types are listed in noise barrier panel specifications.

What does movement do to fixings?

It fatigues them. A fixing that sees a cyclic load twice a day for twenty years accumulates damage even if each cycle is well below its static capacity. The damage shows first as a loose fixing, then as a gap, then as a leak.

Slotted holes with a defined slip and a calibrated tightening torque are the way to manage this. A slot without a specified torque is worse than a round hole, because it can move under load and hammer against the bolt.

How is a slip joint detailed?

With a slotted hole, a washer large enough to bridge the slot, a defined torque that allows sliding without loosening, and a seal that accommodates the movement. The seal is the difficult part, because a gasket that is compressed to seal a static joint will not follow a moving one indefinitely.

Where the joint must remain acoustically closed while moving, a labyrinth or a flexible boot is used rather than a compressed gasket. The labyrinth does not rely on compression and therefore does not relax.

What about very long runs?

They are divided. A run of several hundred metres is broken into structural lengths with expansion joints between them, each length free to move within its own allowance. The division points should coincide with changes in foundation or with posts that are designed to take the movement.

The other long-run issue is the acoustic effect of the joints themselves. A run assembled from many short panels has more joints than one assembled from long panels, and the joints are where leakage concentrates. Long panels reduce joint count but increase the movement each joint has to absorb.

How does temperature affect acoustics?

Two ways. The material properties change, which is a small effect for metal and a larger one for polymers. And the geometry changes, which matters more: a joint that is closed in winter and open in summer changes the leakage area, and leakage is what limits real-world performance at low frequency.

This is one of the reasons a laboratory rating measured at one temperature and an in-situ test measured at another can differ by more than the test uncertainty. The design should not depend on a joint being tight in every season.

What should be checked at handover?

That the expansion joints exist where the drawings show them, that the slots are actually slotted and not filled with weld or grout, that the torque matches the specification, and that the seals are continuous across the joints. Each of these is easy to check and each is commonly found wrong.

Record the ambient temperature at handover, and carry the reading into the maintenance record so a later joint defect can be interpreted. A run installed at one extreme of its temperature range is pre-stressed in one direction, and knowing that helps interpret any movement-related defect later.

ComponentMovement sourceProvision
Long steel runSeasonal expansion of the whole lengthExpansion joint or free end, divided structural lengths
Panel-to-panel jointDifferential movement between adjacent panelsLap or tongue with defined clearance, cover fixed one side
Post baseMovement of the post relative to the foundationSlotted base plate, calibrated torque, grout kept clear of slot
Panel fixingCyclic load from panel movementOversized hole, compliant washer, specified torque
Transparent panelHigh expansion, low point-load toleranceGenerous holes, compliant bedding, wider joint
Acoustic seal at jointJoint opens and closes with temperatureLabyrinth or flexible boot rather than compressed gasket

Standards and references

Structural actions and combinations are taken from EN 1991 and the relevant material parts of EN 1993 and EN 1999. Roadside noise reducing devices are covered by EN 14388, with structural performance under EN 1794-1 and EN 1794-2, and acoustic performance under EN 1793-1 and EN 1793-2. Thermal movement is a serviceability and fatigue consideration rather than an ultimate limit state, which is why it is so often omitted from a design check that focuses on wind. Where panels are polymeric, the manufacturer's design temperature range governs and should be stated on the drawing.

Thermal Movement in Noise Barriers: Joints, Slots and Restraint

Frequently asked questions

How much gap should an expansion joint have?

Enough to absorb the calculated movement at the design temperature range with a margin, and enough to keep the seal compressed at the other extreme. The gap is set at installation temperature, so the installation temperature must be recorded.

Can I weld a long run instead of using joints?

You can, but then the run must be designed for the restrained thermal stress, and the fixings must carry it. In practice welding a long run and then anchoring it rigidly is a reliable way to produce a buckle.

Do aluminium barriers need bigger joints than steel?

Yes, roughly twice the allowance, because the coefficient of expansion is about twice as large. A detail copied from a steel project will be under-sized.

Why did my panels crack at the fixing holes?

Almost always restraint: a hole that was not oversized, a washer that was too small, or a torque that clamped the panel so tightly it could not move. Transparent panels are the usual victim.

Is thermal movement covered by the acoustic test?

No. Laboratory and in-situ acoustic tests are run at ambient conditions on a static assembly. Movement shows up later as a change in leakage, which is why joint details matter more than the test certificate suggests.

Contact Us

Imfornation

Expressway Widening: Upgrading an Existing Noise BarrierBridge Deck Noise Barrier: Load, Movement and AccessGenerator Noise Barrier: Tonal Noise and AirflowPlace of Worship Noise Barrier: Chimes, PA and PlantIndustrial Noise Barrier SystemIntercity Railway Noise Barrier: Mixed Traffic LinesRoad Viaduct Noise Barrier: Deck Edge, Parapet and Load LimitsNoise Barrier Tender Specification: What to State and What Gets MissedNoise Barrier Topic Index: Every Application and StructureLaboratory Noise: Fume Hoods, Compressors and VibrationAt-Grade Railway Noise Barrier: Level Crossings and Track AccessShopping Centre Noise: Rooftop Plant and DeliveriesConstruction Site Noise Barriers: Temporary Screens That Move With the WorksNoise Barrier Inspection and Asset Management: What Fails FirstNoise barriers costNoise Barrier Height or Length: Where the Money Works HarderNoise Barrier Fire Performance: Reaction to Fire and Escape RoutesHighway Interchange Noise Barrier: Multi Level LayoutSchool Noise Barrier: Cutting Traffic Noise at the ClassroomStadium Noise Barrier: Crowd, PA and Plant CompoundsNoise Barrier Access Doors and Gates: Acoustic Openings Done Right5m High Noise BarrierChain Link Fence: Wire, Mesh and Coating SelectionNoise Barrier Installation: Sequence, Posts and Seals3m High Noise BarrierNoise Barrier Wind Load: Posts, Spacing and FoundationsNoise Barrier Acoustic Ratings: DLR, DL-alpha and Insertion LossWind Farm Noise: What a Barrier Can and Cannot DoPermanent or Temporary Noise Barrier: What Actually ChangesRailway Station Noise: Platforms, Plant and ApproachesPhotovoltaic Noise Barrier: Output, Glare and Structural LoadIndustrial Plant Noise Barrier: Boundary Wall and Equipment EnclosureAnti-Climb Fence Specification: 358 Mesh, Paladin Pales and 3D PanelsHospital Noise Barrier: Ward Targets, Height and CleanabilityTunnel Approach Noise Barrier: Open Cut, Portal and Cut-and-CoverRail Overbridge Noise Barrier: When the Bridge Is the SourceAir Source Heat Pump Noise Barrier: Screens and AirflowFreight Railway Noise Barrier: Low Speed, High MassConstruction Hoarding Panels: Wind Load and Site BoundariesTunnel Portal Noise: Hoods, Barriers and AbsorptionTraction Substation Noise: Transformer Hum and Cooling PlantNoise Barrier Site Testing: Why the Installed Wall Differs from the RatingPerforated Metal Noise Barrier: Open Area and AbsorptionNoise Barrier Container Loading: Panels, Posts and PackingLight Rail Noise Barrier: Street Running and Curves